ALLEN BRADLEY 1305 VFD MANUAL PDF

However, using an Allen-Bradley motor with your drive removes the . Н Installation guidelines called out in Appendix D of the User’s Manual. Installation Instructions IN. May, Allen-Bradley. Dynamic Brake. Cat. No. KAA KBA03, KBA06, KBA Table of Contents. Find great deals for Allen Bradley Adjustable Frequency AC Drive User Manual. Shop with confidence on eBay!.

Author: Meztigis Yozshukazahn
Country: El Salvador
Language: English (Spanish)
Genre: Music
Published (Last): 11 September 2004
Pages: 231
PDF File Size: 7.65 Mb
ePub File Size: 4.36 Mb
ISBN: 188-7-26071-936-5
Downloads: 60589
Price: Free* [*Free Regsitration Required]
Uploader: Maurr

Capabilities of drive are different than the master drive.

Allen Bradley Adjustable Frequency AC Drive User Manual | eBay

Check motor for grounded phase. Overspeed Fault – F25 Internal error. Press Enter to continue download. Inspect to ensure that the ambient temperature limit has not been exceeded.

1305 AC Drives

Drive Reset Fault – F22 May occur on power-up. Reprogram Fault – F48 May occur when drive parametersare reset to default settings. Change [Cable Length] to “Long” if applicable. Phase U Fault – F38 A phase to ground default has been detected between the drive and vradley in this phase.

Check for external noise sources.

Save a new profile. Error 5 – Drive is running while attempting download. The Adjustable Frequency AC drive is available with ratings 0. Overtemperature Fault – F8 Temperature sensor detects excessive heat.

  ASUHAN KEPERAWATAN GLOMERULONEFRITIS PDF

Connect proper adapter or change active frequency source. Check [Minimum Freq] and [Maximum Freq] parameters.

Phase V Fault – F39 A phase to ground fault has been detected between the drive and motor in this phase. Inspect the motor and external wiring to the drive output terminals for a shorted condition. Open Pot Fault – F9 An external pot is connected and the ground lead of the pot is disconnected, creating a potential drive overspeed hazard. Reset your drive to the factory default settings.

Overcurrent Vd – Alllen Overcurrent is detected in overcurrent hardware trip circuit. Check programming of [Curr Lim Trip En] parameter. May occur on power-up. Check the external potentiometer circuit at TB2, terminals 1, 2, and 3 for a disconnected current.

Stop drive, then re-run download. A longer acceleration tiime or a lighter load may be required. Download can only occur with the same type of drive. Inspect fault buffer for fault code requiring reset. The last parameter programmed will be displayed on the top line. Unplug the HIM from the cable or drive, then reconnect it.

Check for broken wires, loose connections, or transducer loss at mA input, TB2. Check the motor for grounded phase.

The Adjustable Frequency AC Drive is a variable speed drive designed to control the speed of three-phase AC induction motors in a variety of demanding applications where flexibility, performance and ease of use are essential.

  EL PENSAMIENTO ALEMAN DE KANT A HEIDEGGER PDF

Inspect for proper mounting and spacing. Reset to Default Parameters and Cycle power.

Allen Bradley 1305 Adjustable Frequency AC Drive User Manual

Hz Err Fault – F29 No valid operating frequency. D Micro Programmable Logic Controllers. Phase W Fault – F40 A phase to ground fault has been detected between the drive and motor in this phase.

Inspect for blocked or contaminated heat sink fins. DC Braking cannot be used with a synchronous motor. Check cable connection from main control board to power board. Verify that the parameter has been programmed correctly. If not, manually program any remaining parameters.

Allen Bradley Adjustable Frequency AC Drive AB

Bus overvoltage can also be caused by motor reeneration. If the motor is drawing excessive current, the motor load is excessive and will beadley allow the drive to accelerate to set speed.

An external pot is connected and the ground lead of the pot is disconnected, creating a potential drive overspeed hazard. Fast repairs at low costs.